Pipe Insulation |
All grades of Thermotec pipe insulation have similar performance in relation to operating temperature, thermal conductivity, non-toxicity and moisture absorption.
Fire performance, noise attenuation, chemical resistance, size and wall thickness availability and cost are factors which will usually lead to the selection of a specific grade of Thermotec pipe insulation.
Preformed flame retarded pipe insulation, incorporating unique press seal fastener for quick and easy application on installed pipework.
|
 |
Economic alternative to Quick Seal grade, particularly suitable where pipework is insulated prior to installation.
|
 |
Incorporating a factory applied reinforced aluminium covering for optimum fire performance in accordance with AS 1530.3.
|
 |
Preformed pipe insulation with factory applied heavy duty barium loaded vinyl outer noise barrier. Available in standard and 4-Zero grades.
|
 |
| Thin walled green coloured pipe insulation for domestic applications and dead legs on recirculating hot water systems.
|
 |
Foam sheet cut to predetermined width to exactly fit large diameter pipe. Grooved on inside to eliminate tension and facilitate quick and easy application. Available in standard, 4-Zero or acoustic finish.
|
 |
Pipe Insulation Specifications  |
|
The pipe insulation shall comprise Thermotec Quick Seal/Sealed Tube/4-Zero/Acoustic Standard/Acoustic 4-Zero/Polytube (delete non-applicable grades) fire retarded, closed cell polyethylene foam, having a density of not less than 50kg/m3.
|
|
All insulation shall be installed around the pipework surface as tightly as possible without gaps, with the edges and ends tightly butted together.
|
|
All joints shall be taped using a 48mm adhesive backed PVC tape, or if faced with aluminium foil, joints shall be taped using a 48mm pressure sensitive aluminium tape.
|
|
Where necessary, the pre-formed sections shall be cut (using a sharp knife or scissors) and mitred, to ensure a tight fit around bends and at tees.
|
|
At union flanges, valves and strainers, or any areas where access is required for maintenance, insulation shall incorporate the press seal fastener system.
|
|
Metal sheathing is required for areas where the product is subject to mechanical damage.
|
|
Where supports and spacer blocks are used to support the pipework, the pipe insulation shall be butted up tightly to the spacer blocks and sealed using a silicone sealant.
|
|
If pipework is scheduled to be painted for protection from U.V. and/or identification purposes, the pipe insulation shall be coated using an acrylic based paint in accordance with paint manufacturers recommendations.
|
|
Service penetration units shall be designed to meet a 4 hour fire rating as per AS 1530.4.
|
For further information on this and all other products please contact us.
|