AIR EROSION TEST ON CEILING & RIGID DUCT LINER
Product
TBL 32/50 & TBL 32/25 Black
Method
The test was carried out generally in accordance to the method
described in UL 181 Part 17 "Erosion Test" except that
the velocity used was 13.5 M/Sec.
Requirement
Material for the lining of the air ducts shall not break away,
crack, peel, flake off or show evidence of delamination or continued
erosion when the air is passed through the typical section at
the specified velocity. For the purpose of this requirement, continued
erosion is considered to be either a constant or increasing rate
of erosion.
Result
The product showed no evidence of breaking away, cracking, flake
off, continued erosion or collection of eroded particles on the
collecting screen at the test velocity of 13.5 M/Sec |